The CMS460 system consists of one or several CMS460-D load current evaluators which are able to detect and evaluate load currents in earthed and unearthed power supplies via the associated measuring current transformers. The maximum voltage of the system to be monitored depends on the nominal insulation voltage of the measuring current transformer used in the case of busbar systems, or on the cables or conductors that are routed through.
CTAC… (closed), WR… (rectangular) and WS… (split-core) and WF… (flexible) measuring current transformers are used for alternating and pulsating currents. Any combination of the various measuring current transformer series can be connected to the evaluator measuring channels. Each CMS460-D utilises 12 measuring channels. Up to 90 load current evaluators can be connected via a BMS bus (RS-485 interface with BMS protocol), thereby up to 1080 measuring channels (sub-circuits) can be monitored.
If this product is to be used for fire or plant protection, the frequency response can be set accordingly. The measured currents can be analysed for harmonics.
The CMS460 system consists of one or several CMS460-D load current evaluators which are able to detect and evaluate load currents in earthed and unearthed power supplies via the associated measuring current transformers. The maximum voltage of the system to be monitored depends on the nominal insulation voltage of the measuring current transformer used in the case of busbar systems, or on the cables or conductors that are routed through.
CTAC… (closed), WR… (rectangular) and WS… (split-core) and WF… (flexible) measuring current transformers are used for alternating and pulsating currents. Any combination of the various measuring current transformer series can be connected to the evaluator measuring channels. Each CMS460-D utilises 12 measuring channels. Up to 90 load current evaluators can be connected via a BMS bus (RS-485 interface with BMS protocol), thereby up to 1080 measuring channels (sub-circuits) can be monitored.
If this product is to be used for fire or plant protection, the frequency response can be set accordingly. The measured currents can be analysed for harmonics.
Type | Supply voltage* US | Art. No. |
---|---|---|
CMD460-D-1 | AC 16…72 V, 42…460 Hz/DC 16…94 V | B94053017 |
CMD460-D-2 | AC 70…276 V, 42…460 Hz/DC 70…276 V | B94053018 |
* Absolute values
Power supply
Type | Supply voltage US* | Art. No. |
---|---|---|
DI-1DL (interface repeater) | AC 85…260 V, 50…60 Hz | B95012047 |
* Absolute values
Protocol converters
Type | Description | Supply voltage US* | Art. No. |
---|---|---|---|
COM465IP | Condition Monitor with integrated gateway: Bender system/Ethernet | AC/DC 24…240 V / DC, 50…60 Hz | B95061065 |
CP907-I | Condition Monitor for the connection of Bender BMS devices and universal measuring devices to TCP/IP networks | -- | B95061031 B95061032 |
CP915-I | Condition Monitor for the connection of Bender BMS devices and universal measuring devices to TCP/IP networks | -- | B95061033 B95061034 |
* Absolute values
Measuring current transformers
Type | Internal diameter/mm | Type of construction | Art. No. |
---|---|---|---|
CTAC20 | ø 20 | circular | B98110005 |
CTAC35 | ø 35 | circular | B98110007 |
CTAC60 | ø 60 | circular | B98110017 |
CTAC120 | ø 120 | circular | B98110019 |
CTAC210 | ø 210 | circular | B98110020 |
WR70x175S | 70 x 175 | rectangular | B11738 |
WR70x175SP | 70 x 175 | rectangular | B11790 |
WR115x305S | 115 x 305 | rectangular | B11739 |
WR115x305SP | 115 x 305 | rectangular | B11791 |
WR150x350S | 150 x 350 | rectangular | B911740 |
WR150x350SP | 150 x 350 | rectangular | B911792 |
WR200x500S | 200 x 500 | rectangular | B911763 |
WR200x500SP | 200 x 500 | rectangular | B911793 |
WS20x30 | 20 x 30 | split-core | B98080601 |
WS50x80 | 50 x 80 | split-core | B98080603 |
WS80x120 | 80 x 120 | split-core | B98080606 |
Flexible measuring current transformers (pulsed current sensitive)
Type | Inside diameter/mm | Supply voltage US | Art. No. |
---|---|---|---|
WF170-1 | 170 | DC 9,6…94 V/AC 42…460 Hz 16…72 V | B78080201 |
WF170-2 | 170 | DC 70…300 V/AC 42…460 Hz 70…300 V | B78080202 |
WF250-1 | 250 | DC 9,6…94 V/AC 42…460 Hz 16…72 V | B78080203 |
WF250-2 | 250 | DC 70…300 V/AC 42…460 Hz 70…300 V | B78080204 |
WF500-1 | 500 | DC 9,6…94 V/AC 42…460 Hz 16…72 V | B78080205 |
WF500-2 | 500 | DC 70…300 V/AC 42…460 Hz 70…300 V | B78080206 |
WF800-1 | 800 | DC 9,6…94 V/AC 42…460 Hz 16…72 V | B78080207 |
WF800-2 | 800 | DC 70…300 V/AC 42…460 Hz 70…300 V | B78080208 |
WF1200-1 | 1200 | DC 9,6…94 V/AC 42…460 Hz 16…72 V | B78080209 |
WF1200-2 | 1200 | DC 70…300 V/AC 42…460 Hz 70…300 V | B78080210 |
Name | Category | Size | Language | Timestamp | D-/B-Number |
---|---|---|---|---|---|
CMS4x0 | CE Declarations of Conformity | 82.9 KB | 2022/08/1212.08.2022 | ||
CMS460-D4 | Manuals | 1.3 MB | EN | 2021/02/2626.02.2021 | D00166 |
CMS460-D | Manuals | 3.0 MB | EN | 2019/05/1313.05.2019 | D00045 |
CMS460-D4 | Quickstarts | 627.9 KB | EN | 2024/09/1818.09.2024 | D00166 |
CMS460-D | Datasheets | 453.7 KB | EN | 2019/05/1313.05.2019 | D00045 |
CMS460-D4 | Datasheets | 365.6 KB | EN | 2021/03/0202.03.2021 | D00166 |