The ISOMETER® IR420-D4 monitors the insulation resistance of ungrounded AC control circuits (IT systems) 0…300 V. If the systems to be monitored include DC components, such as switched-mode power supplies or solenoid valves, the display and operating characteristics may be affected.
The display and response values apply to pure AC systems. An external supply voltage allows de-energized systems to be monitored too.
The ISOMETER® IR420-D4 monitors the insulation resistance of ungrounded AC control circuits (IT systems) 0…300 V. If the systems to be monitored include DC components, such as switched-mode power supplies or solenoid valves, the display and operating characteristics may be affected.
The display and response values apply to pure AC systems. An external supply voltage allows de-energized systems to be monitored too.
Type | Nominal system voltage* Un | Supply voltage* US | Response value Ran | System leakage capacitance Ce | Art. No.** |
---|---|---|---|---|---|
IR420-D4-1 | AC 0…300 V, 42…460 Hz | DC 9,6…94 V / AC 16…72 V, 42…460 Hz | 1…200 kΩ | < 20 µF | B71016409 B91016409 |
IR420-D4-2 | AC 0…300 V, 42…460 Hz | DC 70…300 V / AC 70…300 V, 42…46 Hz | 1…200 kΩ | < 20 µF | B71016405 B91016405 |
* absolute values
**(B7… = push-wire terminal / B9… = screw-type terminal)
Type | Art. No. |
---|---|
Mounting clip for screw mounting (one piece per device) | B98060008 |
Mounting frame XM420 | B990994 |
Name | Category | Size | Language | Timestamp | D-/B-Number |
---|---|---|---|---|---|
UKCA - IR42x | Declarations of Conformity | 140.6 KB | 2022/12/2020.12.2022 | ||
IR42x | CE Declarations of Conformity | 94.2 KB | 2022/08/1212.08.2022 | ||
IR420-D4 | Manuals | 2.0 MB | EN | 2024/08/0909.08.2024 | D00037 |
IR420-D4 | Datasheets | 511.8 KB | EN | 2024/07/3030.07.2024 | D00037 |
Changed variants of relays from goldplated to silver-plated contacts | Technical Information | 166.3 KB | EN | 2022/06/2727.06.2022 |